| 机组型号 | 单位 |
CGK
09KVD3C-A
|
CGK
15KVD3C-A
|
CGK
18KVD3C-A
|
CGK
21KVD3C-A
|
CGK-
18KVD3C-A
|
CGK-
21KVD3C-A
|
CGK-
24KVD3C-A
|
CGK-
30KVD3C-A
|
CGK-
39KVD3C-A
|
||
| 电源规格 | 220V~/50Hz | 380V 3N~/50Hz | ||||||||||
| 额定制热量 |
A7℃/
W45℃
|
kW | 9.0 | 15.0 | 18.0 | 21.0 | 18.0 | 21.0 | 24.0 | 30.0 | 39.0 | |
| 额定制热消耗功率 | kW | 2.73 | 4.55 | 5.26 | 6.05 | 5.26 | 6.05 | 6.90 | 9.09 | 12.00 | ||
| COP | W/W | 3.30 | 3.30 | 3.42 | 3.47 | 3.42 | 3.47 | 3.48 | 3.30 | 3.25 | ||
| 名义制热量 |
地暖工况
A-12℃/
W35℃
|
kW | 6.5 | 10.0 | 12.3 | 14.0 | 12.3 | 14.0 | 16.0 | 20.0 | 26.0 | |
| 名义制热消耗功率 | kW | 2.47 | 3.78 | 4.36 | 4.98 | 4.36 | 4.98 | 5.65 | 7.35 | 10.10 | ||
| COP | W/W | 2.63 | 2.65 | 2.82 | 2.81 | 2.82 | 2.81 | 2.83 | 2.72 | 2.57 | ||
| 名义制热量 |
风盘工况
A-12℃/
W41℃
|
kW | 6.6 | 10.2 | 12.4 | 14.2 | 12.4 | 14.2 | 16.1 | 20.2 | 26.3 | |
| 名义制热消耗功率 | kW | 2.75 | 4.20 | 4.85 | 5.58 | 4.85 | 5.58 | 6.32 | 8.18 | 11.10 | ||
| COP | W/W | 2.40 | 2.43 | 2.56 | 2.54 | 2.56 | 2.54 | 2.55 | 2.47 | 2.37 | ||
| 名义制热量 |
暖气片工况
A-12℃/
W50℃
|
kW | 6.6 | 10.2 | 12.4 | 14.2 | 12.4 | 14.2 | 16.1 | 20.2 | 26.3 | |
| 名义制热消耗功率 | kW | 3.26 | 4.83 | 5.70 | 6.56 | 5.70 | 6.56 | 7.42 | 9.40 | 13.15 | ||
| COP | W/W | 2.02 | 2.11 | 2.18 | 2.16 | 2.18 | 2.16 | 2.17 | 2.15 | 2.00 | ||
| 低温制热量 |
地暖工况
A-20℃/
W35℃
|
kW | 5.3 | 8.2 | 10.0 | 11.5 | 10.0 | 11.5 | 13.1 | 16.4 | 21.4 | |
| 低温制热消耗功率 | kW | 2.40 | 3.62 | 4.08 | 4.75 | 4.08 | 4.75 | 5.35 | 6.86 | 9.25 | ||
| COP | W/W | 2.21 | 2.27 | 2.45 | 2.42 | 2.45 | 2.42 | 2.45 | 2.39 | 2.31 | ||
| 低温制热量 |
风盘工况
A-20℃/
W41℃
|
kW | 5.3 | 8.2 | 10.1 | 11.5 | 10.1 | 11.5 | 13.1 | 16.4 | 21.4 | |
| 低温制热消耗功率 | kW | 2.65 | 3.88 | 4.60 | 5.25 | 4.60 | 5.25 | 5.98 | 7.46 | 10.15 | ||
| COP | W/W | 2.00 | 2.11 | 2.20 | 2.19 | 2.20 | 2.19 | 2.19 | 2.20 | 2.11 | ||
| 低温制热量 |
暖气片工况
A-20℃/
W50℃
|
kW | 5.3 | 8.2 | 10.1 | 11.5 | 10.1 | 11.5 | 13.1 | 16.4 | 21.4 | |
| 低温制热消耗功率 | kW | 3.10 | 4.50 | 5.30 | 6.05 | 5.30 | 6.05 | 6.85 | 8.63 | 11.60 | ||
| COP | W/W | 1.71 | 1.82 | 1.91 | 1.90 | 1.91 | 1.90 | 1.91 | 1.90 | 1.84 | ||
| 名义制冷量 |
A35℃/
W7℃
|
kW | 6.0 | 10.0 | 12.0 | 13.0 | 12.0 | 13.0 | 15.0 | 18.8 | 24.0 | |
| 名义制冷消耗功率 | kW | 2.22 | 3.70 | 4.41 | 4.81 | 4.41 | 4.81 | 5.53 | 6.97 | 8.90 | ||
| COP | W/W | 2.70 | 2.70 | 2.72 | 2.70 | 2.72 | 2.70 | 2.71 | 2.70 | 2.70 | ||
| HSPF 35℃/41℃/50℃ |
3.71/3.30/
2.71
|
3.78/3.30/
2.72
|
3.83/3.32/
2.73
|
3.85/3.33/
2.73
|
3.83/3.32/
2.73
|
3.85/3.33/
2.73
|
3.86/3.32/
2.72
|
3.80/3.31/
2.71
|
3.70/3.30/
2.70
|
|||
| APF | 3.30 | 3.31 | 3.32 | 3.34 | 3.32 | 3.34 | 3.34 | 3.31 | 3.30 | |||
| 最大输入功率 | kw | 4 | 5.8 | 6.8 | 7.8 | 7 | 8 | 9 | 12 | 15 | ||
| 最大电流 | A | 20 | 27 | 32 | 36 | 14 | 16 | 18 | 24 | 27 | ||
| 电线规格 | mm² | 4 | 6 | 6 | 10 | 4 | 6 | 6 | 6 | 6 | ||
| 空开规格 | A | 25 | 32 | 40 | 63 | 20 | 25 | 25 | 32 | 32 | ||
| 制冷剂 | R32 | |||||||||||
| 制热/制冷运行范围 | ℃ | -35~35/10~43 | ||||||||||
| 接管管径 | DN25外牙 | DN25外牙 | DN25外牙 | DN25外牙 | DN25外牙 | DN25外牙 | DN25外牙 | DN32外牙 | DN32外牙 | |||
| 水流量 | m3/h | 1.12 | 1.72 | 2.12 | 2.41 | 2.12 | 2.41 | 2.75 | 3.44 | 4.47 | ||
| 水阻力 | kPa | 26 | 20 | 26 | 28 | 26 | 28 | 25 | 28 | 33 | ||
| 制热/制冷噪音 | dB(A) | 57 | 58 | 58 | 59 | 58 | 59 | 60 | 60 | 62 | ||
| 净重 | kg | 71 | 88 | 107 | 110 | 107 | 110 | 115 | 142 | 154 | ||
| 机组尺寸(长*宽*高) | mm |
995×420×
805
|
1066×458×
856
|
995×420×
1375
|
995×420×
1375
|
995×420×
1375
|
995×420×
1375
|
995×420×
1375
|
1070×458×
1572
|
1070×458×
1572
|
||
|
额定制热工况:室外侧干球温度7℃/湿球温度6℃,出水温度45℃。
名义制热工况:室外侧干球温度-12℃/湿球温度-13.5℃,出水温度35/41/50℃。
低温制热工况:室外侧干球温度-20℃,出水温度35/41/50℃。
名义制冷工况:室外侧干球温度35℃,出水温度7℃。
注:机型会不断升级,具体参数请以铭牌为准。
|
||||||||||||
备注:机型会不断升级,具体参数请以铭牌为准